.. _lbl-dldb_damage_FEMA_P58_2nd_D_50_12 ********************************************************* D.50.12 - Electrical Service & Distribution - Low Tension ********************************************************* The following models are available: .. raw:: html

D.50.12.013a | Motor Control Center - Capacity: all - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.013a-Carbon.html **Cost** .. raw:: html :file: D.50.12.013a-Cost.html **Energy** .. raw:: html :file: D.50.12.013a-Energy.html **Time** .. raw:: html :file: D.50.12.013a-Time.html .. raw:: html
.. raw:: html

D.50.12.013b | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.013b-Carbon.html **Cost** .. raw:: html :file: D.50.12.013b-Cost.html **Energy** .. raw:: html :file: D.50.12.013b-Energy.html **Time** .. raw:: html :file: D.50.12.013b-Time.html .. raw:: html
.. raw:: html

D.50.12.013c | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.013c-Carbon.html **Cost** .. raw:: html :file: D.50.12.013c-Cost.html **Energy** .. raw:: html :file: D.50.12.013c-Energy.html **Time** .. raw:: html :file: D.50.12.013c-Time.html .. raw:: html
.. raw:: html

D.50.12.013d | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.013d-Carbon.html **Cost** .. raw:: html :file: D.50.12.013d-Cost.html **Energy** .. raw:: html :file: D.50.12.013d-Energy.html **Time** .. raw:: html :file: D.50.12.013d-Time.html .. raw:: html
.. raw:: html

D.50.12.021a | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.021a-Carbon.html **Cost** .. raw:: html :file: D.50.12.021a-Cost.html **Energy** .. raw:: html :file: D.50.12.021a-Energy.html **Time** .. raw:: html :file: D.50.12.021a-Time.html .. raw:: html
.. raw:: html

D.50.12.021b | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.021b-Carbon.html **Cost** .. raw:: html :file: D.50.12.021b-Cost.html **Energy** .. raw:: html :file: D.50.12.021b-Energy.html **Time** .. raw:: html :file: D.50.12.021b-Time.html .. raw:: html
.. raw:: html

D.50.12.021c | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.021c-Carbon.html **Cost** .. raw:: html :file: D.50.12.021c-Cost.html **Energy** .. raw:: html :file: D.50.12.021c-Energy.html **Time** .. raw:: html :file: D.50.12.021c-Time.html .. raw:: html
.. raw:: html

D.50.12.021d | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.021d-Carbon.html **Cost** .. raw:: html :file: D.50.12.021d-Cost.html **Energy** .. raw:: html :file: D.50.12.021d-Energy.html **Time** .. raw:: html :file: D.50.12.021d-Time.html .. raw:: html
.. raw:: html

D.50.12.023a | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023a-Carbon.html **Cost** .. raw:: html :file: D.50.12.023a-Cost.html **Energy** .. raw:: html :file: D.50.12.023a-Energy.html **Time** .. raw:: html :file: D.50.12.023a-Time.html .. raw:: html
.. raw:: html

D.50.12.023b | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023b-Carbon.html **Cost** .. raw:: html :file: D.50.12.023b-Cost.html **Energy** .. raw:: html :file: D.50.12.023b-Energy.html **Time** .. raw:: html :file: D.50.12.023b-Time.html .. raw:: html
.. raw:: html

D.50.12.023c | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023c-Carbon.html **Cost** .. raw:: html :file: D.50.12.023c-Cost.html **Energy** .. raw:: html :file: D.50.12.023c-Energy.html **Time** .. raw:: html :file: D.50.12.023c-Time.html .. raw:: html
.. raw:: html

D.50.12.023d | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023d-Carbon.html **Cost** .. raw:: html :file: D.50.12.023d-Cost.html **Energy** .. raw:: html :file: D.50.12.023d-Energy.html **Time** .. raw:: html :file: D.50.12.023d-Time.html .. raw:: html
.. raw:: html

D.50.12.023e | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023e-Carbon.html **Cost** .. raw:: html :file: D.50.12.023e-Cost.html **Energy** .. raw:: html :file: D.50.12.023e-Energy.html **Time** .. raw:: html :file: D.50.12.023e-Time.html .. raw:: html
.. raw:: html

D.50.12.023f | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023f-Carbon.html **Cost** .. raw:: html :file: D.50.12.023f-Cost.html **Energy** .. raw:: html :file: D.50.12.023f-Energy.html **Time** .. raw:: html :file: D.50.12.023f-Time.html .. raw:: html
.. raw:: html

D.50.12.023g | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023g-Carbon.html **Cost** .. raw:: html :file: D.50.12.023g-Cost.html **Energy** .. raw:: html :file: D.50.12.023g-Energy.html **Time** .. raw:: html :file: D.50.12.023g-Time.html .. raw:: html
.. raw:: html

D.50.12.023h | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023h-Carbon.html **Cost** .. raw:: html :file: D.50.12.023h-Cost.html **Energy** .. raw:: html :file: D.50.12.023h-Energy.html **Time** .. raw:: html :file: D.50.12.023h-Time.html .. raw:: html
.. raw:: html

D.50.12.023i | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023i-Carbon.html **Cost** .. raw:: html :file: D.50.12.023i-Cost.html **Energy** .. raw:: html :file: D.50.12.023i-Energy.html **Time** .. raw:: html :file: D.50.12.023i-Time.html .. raw:: html
.. raw:: html

D.50.12.023j | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023j-Carbon.html **Cost** .. raw:: html :file: D.50.12.023j-Cost.html **Energy** .. raw:: html :file: D.50.12.023j-Energy.html **Time** .. raw:: html :file: D.50.12.023j-Time.html .. raw:: html
.. raw:: html

D.50.12.023k | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023k-Carbon.html **Cost** .. raw:: html :file: D.50.12.023k-Cost.html **Energy** .. raw:: html :file: D.50.12.023k-Energy.html **Time** .. raw:: html :file: D.50.12.023k-Time.html .. raw:: html
.. raw:: html

D.50.12.023l | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.023l-Carbon.html **Cost** .. raw:: html :file: D.50.12.023l-Cost.html **Energy** .. raw:: html :file: D.50.12.023l-Energy.html **Time** .. raw:: html :file: D.50.12.023l-Time.html .. raw:: html
.. raw:: html

D.50.12.031a | Distribution Panel - Capacity: 100 to <350 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.031a-Carbon.html **Cost** .. raw:: html :file: D.50.12.031a-Cost.html **Energy** .. raw:: html :file: D.50.12.031a-Energy.html **Time** .. raw:: html :file: D.50.12.031a-Time.html .. raw:: html
.. raw:: html

D.50.12.031b | Distribution Panel - Capacity: 350 to <750 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.031b-Carbon.html **Cost** .. raw:: html :file: D.50.12.031b-Cost.html **Energy** .. raw:: html :file: D.50.12.031b-Energy.html **Time** .. raw:: html :file: D.50.12.031b-Time.html .. raw:: html
.. raw:: html

D.50.12.031c | Distribution Panel - Capacity: 750 to <1200 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.031c-Carbon.html **Cost** .. raw:: html :file: D.50.12.031c-Cost.html **Energy** .. raw:: html :file: D.50.12.031c-Energy.html **Time** .. raw:: html :file: D.50.12.031c-Time.html .. raw:: html
.. raw:: html

D.50.12.031d | Distribution Panel - Capacity: 1200 to 2000 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Not designed for seismic loads | Seismic Installation Conditions: Unanchored equipment that is not vibration isolated Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.031d-Carbon.html **Cost** .. raw:: html :file: D.50.12.031d-Cost.html **Energy** .. raw:: html :file: D.50.12.031d-Energy.html **Time** .. raw:: html :file: D.50.12.031d-Time.html .. raw:: html
.. raw:: html

D.50.12.033a | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033a-Carbon.html **Cost** .. raw:: html :file: D.50.12.033a-Cost.html **Energy** .. raw:: html :file: D.50.12.033a-Energy.html **Time** .. raw:: html :file: D.50.12.033a-Time.html .. raw:: html
.. raw:: html

D.50.12.033b | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033b-Carbon.html **Cost** .. raw:: html :file: D.50.12.033b-Cost.html **Energy** .. raw:: html :file: D.50.12.033b-Energy.html **Time** .. raw:: html :file: D.50.12.033b-Time.html .. raw:: html
.. raw:: html

D.50.12.033c | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 225 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033c-Carbon.html **Cost** .. raw:: html :file: D.50.12.033c-Cost.html **Energy** .. raw:: html :file: D.50.12.033c-Energy.html **Time** .. raw:: html :file: D.50.12.033c-Time.html .. raw:: html
.. raw:: html

D.50.12.033d | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033d-Carbon.html **Cost** .. raw:: html :file: D.50.12.033d-Cost.html **Energy** .. raw:: html :file: D.50.12.033d-Energy.html **Time** .. raw:: html :file: D.50.12.033d-Time.html .. raw:: html
.. raw:: html

D.50.12.033e | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033e-Carbon.html **Cost** .. raw:: html :file: D.50.12.033e-Cost.html **Energy** .. raw:: html :file: D.50.12.033e-Energy.html **Time** .. raw:: html :file: D.50.12.033e-Time.html .. raw:: html
.. raw:: html

D.50.12.033f | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 400 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033f-Carbon.html **Cost** .. raw:: html :file: D.50.12.033f-Cost.html **Energy** .. raw:: html :file: D.50.12.033f-Energy.html **Time** .. raw:: html :file: D.50.12.033f-Time.html .. raw:: html
.. raw:: html

D.50.12.033g | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033g-Carbon.html **Cost** .. raw:: html :file: D.50.12.033g-Cost.html **Energy** .. raw:: html :file: D.50.12.033g-Energy.html **Time** .. raw:: html :file: D.50.12.033g-Time.html .. raw:: html
.. raw:: html

D.50.12.033h | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033h-Carbon.html **Cost** .. raw:: html :file: D.50.12.033h-Cost.html **Energy** .. raw:: html :file: D.50.12.033h-Energy.html **Time** .. raw:: html :file: D.50.12.033h-Time.html .. raw:: html
.. raw:: html

D.50.12.033i | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 800 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033i-Carbon.html **Cost** .. raw:: html :file: D.50.12.033i-Cost.html **Energy** .. raw:: html :file: D.50.12.033i-Energy.html **Time** .. raw:: html :file: D.50.12.033i-Time.html .. raw:: html
.. raw:: html

D.50.12.033j | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033j-Carbon.html **Cost** .. raw:: html :file: D.50.12.033j-Cost.html **Energy** .. raw:: html :file: D.50.12.033j-Energy.html **Time** .. raw:: html :file: D.50.12.033j-Time.html .. raw:: html
.. raw:: html

D.50.12.033k | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033k-Carbon.html **Cost** .. raw:: html :file: D.50.12.033k-Cost.html **Energy** .. raw:: html :file: D.50.12.033k-Energy.html **Time** .. raw:: html :file: D.50.12.033k-Time.html .. raw:: html
.. raw:: html

D.50.12.033l | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

| Costing is per unit and is based upon 1600 Amp. | Construction Quality: Normal - Designed for seismic loads but no special seismic certification | Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints | Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component. Suggested Block Size: 1 EA The following repair consequences are available for this model: **Carbon** .. raw:: html :file: D.50.12.033l-Carbon.html **Cost** .. raw:: html :file: D.50.12.033l-Cost.html **Energy** .. raw:: html :file: D.50.12.033l-Energy.html **Time** .. raw:: html :file: D.50.12.033l-Time.html .. raw:: html