D.20.21 - Domestic Water Distribution - Cold Water

The following models are available:

D.20.21.011a | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC A or B, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC A or B
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.011b | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC A or B, BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC A or B
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.012a | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC C, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC C
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.012b | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC C, BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC C
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.013a | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC D, E, or F, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

24600.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)2.254.1 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.013b | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC D, E, or F, BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

11.522.500.20.40.60.81LS1LimitStateDS1DamageState(s)1.5 MedianCapacitylognormal CapacityDistribution0.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)*

D.20.21.014a | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC D, E, or F (OSHPD or sim), PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Special Regulation (e.g. OSHPD) for piping installations
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

24600.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)2.254.1 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.014b | Cold or Hot Potable - Small Diameter Threaded Steel - (2.5 inches in diameter or less), SDC D, E, or F (OSHPD or sim), BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Special Regulation (e.g. OSHPD) for piping installations
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

11.522.500.20.40.60.81LS1LimitStateDS1DamageState(s)1.5 MedianCapacitylognormal CapacityDistribution0.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)*

D.20.21.021a | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC A or B, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC A or B
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.022a | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC C, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC C
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

123400.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.6 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.023a | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC D,E,F, PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

24600.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)2.254.1 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.023b | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC D,E,F, BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Normal
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

12300.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.25 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.024a | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC D,E,F (OSPHD or sim), PIPING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Special Regulation (e.g. OSHPD) for piping installations
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

24600.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)2.254.1 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**

D.20.21.024b | Cold or Hot Potable Water Piping (dia > 2.5 inches), SDC D,E,F (OSPHD or sim), BRACING FRAGILITY

Potable water. Costing based upon 1000 ft segments.
Construction Quality: Special Regulation (e.g. OSHPD) for piping installations
Seismic Installation Conditions: SDC D, E or F (high seismic design)
Notes: Consequence is for piping only. Enter floor wetting consequence seperately. Cost includes allowance for MEP relocation to perform work.

Suggested Block Size: 1000 LF

12300.20.40.60.81LS1LS2LimitStateDS1DS2DamageState(s)1.52.25 MedianCapacitylognormallognormal CapacityDistribution0.40.4 CapacityDispersion
Peak Floor Acceleration [g]P(LS≥ls​i)**