D.50.92 - Other Electrical SystemsΒΆ

The following models are available:

D.50.92.011a | Battery Rack - Capacity: all - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.013a | Battery Rack - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.013b | Battery Rack - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.013c | Battery Rack - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.021a | Battery Charger - Capacity: all - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.023a | Battery Charger - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.023b | Battery Charger - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.023c | Battery Charger - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.031a | Diesel generator - Capacity: 100 to <350 kVA - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.031b | Diesel generator - Capacity: 350 to <750 kVA - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.031c | Diesel generator - Capacity: 750 to 1200 kVA - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.031d | Diesel generator - Capacity: 1200 to 2000 kVa - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032a | Diesel generator - Capacity: 100 to <350 kVA - Vibration isolated equipment that is not snubbed or restrained - Anchorage fragility only

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032b | Diesel generator - Capacity: 100 to <350 kVA - Vibration isolated equipment that is not snubbed or restrained - Equipment fragility only

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032c | Diesel generator - Capacity: 100 to <350 kVA - Vibration isolated equipment that is not snubbed or restrained - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032d | Diesel generator - Capacity: 350 to <750 kVA - Vibration isolated equipment that is not snubbed or restrained - Anchorage fragility only

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032e | Diesel generator - Capacity: 350 to <750 kVA - Vibration isolated equipment that is not snubbed or restrained - Equipment fragility only

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032f | Diesel generator - Capacity: 350 to <750 kVA - Vibration isolated equipment that is not snubbed or restrained - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032g | Diesel generator - Capacity: 750 to 1200 kVA - Vibration isolated equipment that is not snubbed or restrained - Anchorage fragility only

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032h | Diesel generator - Capacity: 750 to 1200 kVA - Vibration isolated equipment that is not snubbed or restrained - Equipment fragility only

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032i | Diesel generator - Capacity: 750 to 1200 kVA - Vibration isolated equipment that is not snubbed or restrained - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032j | Diesel generator - Capacity: 1200 to 2000 kVa - Vibration isolated equipment that is not snubbed or restrained - Anchorage fragility only

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032k | Diesel generator - Capacity: 1200 to 2000 kVa - Vibration isolated equipment that is not snubbed or restrained - Equipment fragility only

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.032l | Diesel generator - Capacity: 1200 to 2000 kVa - Vibration isolated equipment that is not snubbed or restrained - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Vibration isolated equipment that is not snubbed or restrained
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033a | Diesel generator - Capacity: 100 to <350 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033b | Diesel generator - Capacity: 100 to <350 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033c | Diesel generator - Capacity: 100 to <350 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 250 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033d | Diesel generator - Capacity: 350 to <750 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033e | Diesel generator - Capacity: 350 to <750 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033f | Diesel generator - Capacity: 350 to <750 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033g | Diesel generator - Capacity: 750 to 1200 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033h | Diesel generator - Capacity: 750 to 1200 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033i | Diesel generator - Capacity: 750 to 1200 kVA - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1000 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033j | Diesel generator - Capacity: 1200 to 2000 kVa - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033k | Diesel generator - Capacity: 1200 to 2000 kVa - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.92.033l | Diesel generator - Capacity: 1200 to 2000 kVa - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1500 kVa.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time