D.50.12 - Electrical Service & Distribution - Low TensionΒΆ

The following models are available:

D.50.12.013a | Motor Control Center - Capacity: all - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.013b | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.013c | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.013d | Motor Control Center - Capacity: all - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.021a | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.021b | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.021c | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.021d | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023a | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023b | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023c | Low Voltage Switchgear - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023d | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023e | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023f | Low Voltage Switchgear - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023g | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023h | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023i | Low Voltage Switchgear - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023j | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023k | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.023l | Low Voltage Switchgear - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.031a | Distribution Panel - Capacity: 100 to <350 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.031b | Distribution Panel - Capacity: 350 to <750 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.031c | Distribution Panel - Capacity: 750 to <1200 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.031d | Distribution Panel - Capacity: 1200 to 2000 Amp - Unanchored equipment that is not vibration isolated - Equipment fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Not designed for seismic loads
Seismic Installation Conditions: Unanchored equipment that is not vibration isolated

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033a | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033b | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033c | Distribution Panel - Capacity: 100 to <350 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 225 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033d | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033e | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033f | Distribution Panel - Capacity: 350 to <750 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 400 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033g | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033h | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033i | Distribution Panel - Capacity: 750 to <1200 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 800 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033j | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Anchorage fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033k | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Equipment fragility only

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time


D.50.12.033l | Distribution Panel - Capacity: 1200 to 2000 Amp - Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints - Combined anchorage/isolator & equipment fragility

Costing is per unit and is based upon 1600 Amp.
Construction Quality: Normal - Designed for seismic loads but no special seismic certification
Seismic Installation Conditions: Equipment that is either hard anchored or is vibration isolated with seismic snubbers/restraints
Notes: User to provide median demand and dispersion values. The values listed are default PACT values and do not represent the response of this component.

Suggested Block Size: 1 EA

The following repair consequences are available for this model:

Carbon

Cost

Energy

Time